| AWG 
                          18 (Solid) Bare Copper Shielded |  | 
                     
                      | Aero 
                        P/N | # 
                        of Pair | Insulation 
                        Thickness (inches) | Jacket 
                        Thickness (inches) | Jacket 
                        O.D. (inches) | Lbs 
                        / 1000' | 
                     
                      | 2230/1 | 2 | .006 | .010 | .206 | 33 | 
                     
                      | 2430/1 | 4 | .006 | .010 | .242 | 57 | 
                     
                      | 2830/1 | 8 | .006 | .010 | .319 | 107 | 
                     
                      | 2030/1 | 10 | .006 | .012 | .366 | 131 | 
                     
                      | 2130-25/1 | 25 | .006 | .015 | .533 | 313 | 
                     
                      |  |  |  |  |  |  | 
                  
                  
                     
                      | AWG 
                          18 (Solid) Bare Copper Unshielded |  | 
                     
                      | Aero 
                        P/N | # 
                        of Pair | Insulation 
                        Thickness (inches) | Jacket 
                        Thickness (inches) | Jacket 
                        O.D. (inches) | Lbs 
                        / 1000' | 
                     
                      | 2231/1 | 2 | .006 | .010 | .202 | 28 | 
                     
                      | 2431/1 | 4 | .006 | .010 | .238 | 52 | 
                     
                      | 2631/1 | 6 | .006 | .012 | .284 | 78 | 
                     
                      | 2031/1 | 10 | .006 | .012 | .362 | 125 | 
                     
                      |  |  |  |  |  |  | 
                  
                  
                     
                      | AWG 
                          18 (Solid) Bare Copper Ind. Shielded |  | 
                     
                      | Aero 
                        P/N | # 
                        of Pair | Insulation 
                        Thickness (inches) | Jacket 
                        Thickness (inches) | Jacket 
                        O.D. (inches) | Lbs 
                        / 1000' | 
                     
                      | 2232/1† | 2 | .006 | .010 | .235 | 34 | 
                     
                      |  |  |  |  |  |  | 
                  
                  
                     
                      | AWG 
                          16 (Solid) Bare Copper Shielded |  | 
                     
                      | Aero 
                        P/N | # 
                        of Pair | Insulation 
                        Thickness (inches) | Jacket 
                        Thickness (inches) | Jacket 
                        O.D. (inches) | Lbs 
                        / 1000' | 
                     
                      | 2220/1 | 2 | .007 | .010 | .251 | 51 | 
                     
                      |  |  |  |  |  |  | 
                  
                  
                     
                      | AWG 
                          16 (Solid) Bare Copper Unshielded |  | 
                     
                      | Aero 
                        P/N | # 
                        of Pair | Insulation 
                        Thickness (inches) | Jacket 
                        Thickness (inches) | Jacket 
                        O.D. (inches) | Lbs 
                        / 1000' | 
                     
                      | 2221/1 | 2 | .007 | .010 | .247 | 43 | 
                     
                      |  |  |  |  |  |  | 
                  
                  
                    
                     
                      
                    
                     
                      |  |  | 
                     
                      | Specifications |  | 
                     
                      | Conductor:Solid B.C.
 Insulation:FEP or
 Halar (ECTFE) Add "HL" to P/N
 Color Code:Chart 3
 † Common drain wire Jackets Available:FEP (200°C) or
 PVDF (150°C) Add "K" to P/N or
 Plenum PVC Jacket available
 Industry Approvals:NEC Article 725-CL2P or
 NEC Article 800-CMP
 PCC FT6-C(UL) (CMP only)
 Impedance: (FEP only)AWG 18:
 Unshielded 72 Ohms Nom.
 Overall Shield 70 Ohms Nom.
 Individual Shielded 37 Ohms Nom.
 AWG 16:
 Unshielded 70 Ohms Nom.
 Overall Shield 68 Ohms Nom.
 |  Vel. of Propagation: (FEP 
                          only)69% Nom.
 Capacitance: (FEP only)AWG 18:
 Unshielded 20 pF/ft.
 Overall Shield 22 pF/ft
 Individual Shield 40 pF/ft
 AWG 16:
 Unshielded 21 pF/ft
 Overall Shield 23 pF/ft
 Temperature Rating:-80°C to +200°C (FEP/FEP)
 -20°C to +150°C (FEP/PVDF)
 -20°C to +150°C (Halar/PVDF)
 Put Ups:1000 Feet (+/- 10%)
 (Available in Bulk Reels)
 |