mid capacitance plenum cable custom cable design
   

Mid-Capacitance Plenum Cable
MultiPair / Stranded / Foil Shielded
(UL) CL2P or CMP
200°C, 150°C or 75°C

plenum cable
Color Code Chart

 

 

AWG 28 (7x36) Tinned Copper

 
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2196-13 13 .006 .010 .213 30
AWG 24 (7x32) Tinned Copper
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2270 2 .006 .010 .150 13
2370 3 .006 .010 .159 17
2370* 3 .006 .010 .159 20
2470 4 .006 .010 .175 21
2470* 4 .006 .010 .175 24
2570 5 .006 .010 .197 26
2570* 5 .006 .010 .197 29
2670 6 .006 .010 .204 30
2770 7 .006 .010 .204 34
2870 8 .006 .010 .226 38
2970 9 .006 .010 .240 42
2070 10 .006 .010 .258 47
2170 12.5 .006 .010 .269 57
2170-15 15 .006 .010 .294 69
2170-16 16 .006 .010 .309 73
2170-18 18 .006 .012 .316 81
2170-18.5 18.5 .006 .012 .316 83
2170-19 19 .006 .010 .316 85
2170-20 20 .006 .012 .323 89
2170-22 22 .006 .010 .345 97
2170-25 25 .006 .010 .374 110
2170-31 31 .006 .015 .405 137
Specifications

Conductor:
Stranded T.C.

Insulation:
FEP

Color Code:
Chart 3

Shield:
Aluminum/Mylar

Jackets Available:
FEP (200°C)
E-CTFE (150°C) Add "K" to P/N
Aeroflex (75°C) Add PV to P/N

Industry Approvals:
NEC Article 725-CL2P
NEC Article 800-CMP
C(UL) (CMP only)

Impedance: (FEP only)
(AWG 28) 110 Ohms Nom.
(AWG 24) 90 Ohms Nom.

Vel. of Propagation: (FEP only)
69% Nom.

Capacitance: (FEP only)
(AWG 28) 13.4 pF/ft Nom.
(AWG 24) 16.2 pF/ft Nom.

Temperature Rating:
-80°C to +200°C (FEP/FEP)
-40°C to +150°C (FEP/E-CTFE)

Put Ups:
1000 Feet (+/- 10%)
(Available in Bulk Reels)

Add to P/N:
*RD = Red Jacket, CMP 200°C
*KRD = Red Jacket, CMP 150°C
*PV = Aeroflex Jacket, 75°C

 
[Profile] [Catalog] [Custom Cable Worksheet] [Services] [Newsletter]