plenum cable custom cable design
   

Plenum Cable
MultiPair / Solid / Shielded & Unshielded
(UL) CL2P or CMP
200°C or 150°C

plenum cable
Color Code Chart

 

 

AWG 18 (Solid) Bare Copper Shielded

 
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2230/1 2 .006 .010 .206 33
2430/1 4 .006 .010 .242 57
2830/1 8 .006 .010 .319 107
2030/1 10 .006 .012 .366 131
2130-25/1 25 .006 .015 .533 313
           
           
AWG 18 (Solid) Bare Copper Unshielded
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2231/1 2 .006 .010 .202 28
2431/1 4 .006 .010 .238 52
2631/1 6 .006 .012 .284 78
2031/1 10 .006 .012 .362 125
           
           
AWG 18 (Solid) Bare Copper Ind. Shielded
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2232/1§ 2 .006 .010 .235 34
           
           
AWG 16 (Solid) Bare Copper Shielded
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2220/1 2 .007 .010 .251 51
           
           
AWG 16 (Solid) Bare Copper Unshielded
Aero P/N # of Pairs Insulation
Thickness
(inches)
Jacket
Thickness
(inches)
Jacket O.D.
(inches)
Lbs/1000'
2221/1 2 .007 .010 .247 43
Specifications

Conductor:
Solid B.C.

Insulation:
FEP or
Halar (ECTFE) Add "HL" to P/N

Color Code:
Chart 3 Except:

§=Common drain wire

Jackets Available:
FEP (200°C) or
PVDF (150°C) Add "K" to P/N or
Plenum PVC Jacket available

Industry Approvals:
NEC Article 725-CL2P or
NEC Article 800-CMP
PCC FT6-C(UL) (CMP only)

Impedance: (FEP only)
AWG 18:
Unshielded 72 Ohms Nom.
Overall Shield 70 Ohms Nom.
Individual Shielded 37 Ohms Nom.
AWG 16:
Unshielded 70 Ohms Nom.
Overall Shield 68 Ohms Nom.

Vel. of Propagation: (FEP only)
69% Nom.

Capacitance: (FEP only)
AWG 18:
Unshielded 20 pF/ft.
Overall Shield 22 pF/ft
Individual Shield 40 pF/ft
AWG 16:
Unshielded 21 pF/ft
Overall Shield 23 pF/ft

Temperature Rating:
-80°C to +200°C (FEP/FEP)
-20°C to +150°C (FEP/PVDF)
-20°C to +150°C (Halar/PVDF)

Put Ups:
1000 Feet (+/- 10%)
(Available in Bulk Reels)

 
[Profile] [Catalog] [Custom Cable Worksheet] [Services] [Newsletter]
[Contact Us] [On The Shelf Inventory]